How to run a real-fluid cycle 01 Pick the cycle. Rankine opens at 3 MPa / 350 °C into a 75 kPa condenser — the classic textbook example; the refrigerator preset is R134a at −20 °C evaporating and 40 °C condensing. 02 Set pressures and temperatures. Boiler pressure must exceed condenser pressure; a turbine-inlet temperature below saturation is snapped to saturated vapour with a warning rather than extrapolated. 03 Read the states in order. State 1 is saturated liquid leaving the condenser, 2 the pump exit, 3 the turbine inlet, 4 the turbine exit; wet exits are marked twoPhase with their quality. 04 Add one option at a time. Reheat sets an intermediate pressure and a second turbine inlet; regeneration sets an extraction pressure. Compare each against the plain cycle before combining. 05 Scale to power or load. A mass flow turns work per kilogram into kW; a cooling load turns COP into compressor power.
Worked readouts
Cycle · input
Readout
Rankine · 3 MPa / 350 °C → 75 kPa
η 25.7976 % , w<sub>turb</sub> 686.20 kJ/kg , w<sub>pump</sub> 3.03 kJ/kg , q<sub>in</sub> 2648.16 kJ/kg , exit quality 0.86261 , Carnot 41.4411 % ; 20 kg/s gives 13.66 MW
Rankine · 15 MPa / 600 °C → 10 kPa, simple
η 41.5921 % , exit quality 0.71991
The same cycle with reheat at 2 MPa
η 43.4712 % , exit quality 0.91991
Rankine regenerative · 4 MPa / 450 °C, extraction 400 kPa
η 37.8386 % , extraction fraction 0.166622 , exit quality 0.81033
R134a fridge · −20 °C / 40 °C
COP 2.5803 , q<sub>evap</sub> 130.15 kJ/kg , throttle quality 0.38874 , COP<sub>HP</sub> 3.5803
R134a air conditioner · 5 °C / 45 °C
COP 4.7721 , throttle quality 0.29321
The engine's states for the Cengel preset are h₁ = 384.44 , h₂ = 387.47 , h₃ = 3035.64 , h₄ = 2349.44 kJ/kg at a condenser saturation temperature of 364.91 K . The reheat comparison is the sharper story: efficiency rises 1.88 points and exit moisture falls from 28 % to 8 % .
What the state points mean The pump raises liquid pressure almost isentropically — it costs only 3.03 kJ/kg because liquids are nearly incompressible — then the boiler adds heat at constant pressure, first to boil and then to superheat. The turbine expands back to condenser pressure and ideally exits with the inlet entropy, 6.5982 kJ/(kg·K) ; interpolation inside the dome gives quality 0.8626 , meaning 14 % of the mass is liquid droplets at turbine speed. Real plants prefer exits above roughly 0.88 and use reheat or higher superheat to get there. The condenser then removes 1965.0 kJ/kg and returns saturated liquid.
Efficiency follows the Carnot logic but reads much lower than the ideal layer because heat is added over a boiling range: 25.7976 % against a bound of 41.4411 % is a second-law efficiency of 62.25 % . On the refrigeration side the four states are saturated vapour at 238.41 kJ/kg , superheated discharge at 288.85 kJ/kg , saturated liquid at 108.26 kJ/kg , and a two-phase mix after the throttle at quality 0.38874 . COP is q<sub>evap</sub>/w<sub>comp</sub> = 130.15 / 50.44 = 2.5803 ; a heat pump counts the condenser heat and reads 3.5803 , the refrigeration COP plus one. The 61.16 % second-law efficiency belongs to the refrigeration COP 2.5803 against its Carnot COP of 4.2192 .
Limits and edges
The built-in tables are a fallback, and the run says so. Water and R134a are interpolated from a small saturation grid with an ideal-gas superheat polynomial; enthalpy and entropy carry roughly 0.5–1 % error, and the Cengel preset lands at 25.7976 % against the textbook's ~26.0 %. Loading CoolProp replaces the tables with Helmholtz-equation properties and tightens the comparison.
One fluid pair, one heater. R134a is the only refrigerant and regeneration is a single open feedwater heater; there is no two-stage compression, flash chamber or organic Rankine fluid. What it does not do. It does not size boilers or turbines, model pressure drops, or predict off-design behaviour. For combustion-air cycles use the Ideal-gas tab ; for dynamic models, the Engineering Lab .
The quality cliff Turbine exit quality is the number that ends design discussions, and it is easy to ignore because efficiency looks fine without it. The simple 15 MPa / 600 °C cycle reads 41.5921 % but exits at quality 0.71991 — the last stages would erode. Adding reheat reads 43.4712 % and raises the exit to 0.91991 . The second trap is assuming a higher-efficiency configuration is always better: regeneration here runs at 37.8386 % , below the simple cycle's 41.5921 % at the same pressure, because the extraction bleeds work away from the turbine; what it buys is a warmer feedwater, not a higher number. The third is the R134a throttle: state 4 is intentionally two-phase at quality 0.38874 , and an expansion device is not a turbine — treating it as one would double-count work the cycle never gets back.
Where it earns its place Checking a textbook steam cycle Cengel's 3 MPa / 350 °C example is the shipping preset: quality 0.86261 , w<sub>turb</sub> 686.20 kJ/kg , w<sub>pump</sub> 3.03 kJ/kg , η 25.7976 % , net power 13.66 MW at 20 kg/s. The gap against the book is visible and attributable.
Estimating a fridge or air conditioner The −20 / 40 °C preset gives COP 2.5803 and, with a 3.5 kW load, a compressor draw of 1.36 kW ; the 5 / 45 °C preset gives COP 4.7721 . Both are ideal-cycle ceilings, a useful calibration before adding real losses.
Privacy The tables, interpolation and plots run locally in your browser; only the optional CoolProp download touches the network, and the calculation still runs locally.
References
Wikipedia, Rankine cycle , en.wikipedia.org (访问日期:2026-10-07)— pump, boiler, turbine and condenser states.
Wikipedia, Vapor-compression refrigeration , en.wikipedia.org (访问日期:2026-10-07)— the four-state cycle, COP and the throttle.
Wikipedia, Superheated steam , en.wikipedia.org (访问日期:2026-10-07)— why superheat and reheat protect the turbine.
Wikipedia, Saturation (thermodynamics) , en.wikipedia.org (访问日期:2026-10-07)— saturation tables, quality and the dome.
Bell et al., CoolProp , coolprop.org (访问日期:2026-10-07)— the optional Helmholtz-equation property backend.
Calculators in this hub
Hand-picked tools, one click away. The mini versions compute live and carry your values into the full calculator.
Sources & review
Reviewed by CalcX Editorial Team
Updated 2026-10-07